Basic Info.
Model NO.
ACME60-332000
Link of Transformation
AC-DC-AC Variable-Frequency Drive
Nature of DC Power
Current Variable-Frequency Drive
Function
Simple Type
Brand
Acme
Power
200kVA
Circuit Model
IGBT/Spwm
Input
220V/380V
Frequency
50/60Hz
Output
220/380V
Phase
Three
Current
556A
Voltage Stability
1%
Frequency Stability
0.01%
Thd
2%
Reaction Time
2ms
Transport Package
Wooden Box
Specification
200kva
Trademark
ACME
Origin
Jinan
HS Code
8504401990
Production Capacity
500PCS/Month
Product Description
Product introduction
Product introduction
ACME60 series variable frequency power supply is specially designed and manufactured for 60Hz import and export equipment, can be used as the import of 60Hz electrical equipment and production line power supply, can also be used as a test power supply for export electrical products production line. In line with the European and American power supply system, the design of the national standard "GB/T 260.3-2003", "GB/T260.2-2003", the national military standard "GJB181A-2003", "Jb G572-88" technical conditions. Its main features are the provision of low harmonic distortion, high stability frequency and regulatory rate of pure and reliable sine wave power output. In addition, it can support high frequencies of 400Hz avionics and military equipment. ACME60 series of variable frequency power supply can solve almost all power supply problems, such as high voltage, low voltage, voltage instantaneous drop, reduced oscillation, high voltage pulse, voltage fluctuation, surge voltage, harmonic distortion, clutter interference, frequency fluctuations and other power supply problems.
Technical features:
Product introduction
ACME60 series variable frequency power supply is specially designed and manufactured for 60Hz import and export equipment, can be used as the import of 60Hz electrical equipment and production line power supply, can also be used as a test power supply for export electrical products production line. In line with the European and American power supply system, the design of the national standard "GB/T 260.3-2003", "GB/T260.2-2003", the national military standard "GJB181A-2003", "Jb G572-88" technical conditions. Its main features are the provision of low harmonic distortion, high stability frequency and regulatory rate of pure and reliable sine wave power output. In addition, it can support high frequencies of 400Hz avionics and military equipment. ACME60 series of variable frequency power supply can solve almost all power supply problems, such as high voltage, low voltage, voltage instantaneous drop, reduced oscillation, high voltage pulse, voltage fluctuation, surge voltage, harmonic distortion, clutter interference, frequency fluctuations and other power supply problems.
Technical features:
- Multi-functional AC source test equipment - simulates different types of power supply around the world, supporting 400HZ frequency of defense military detection, avionics and navigation, communications and other equipment.
- Produces a pure AC output power supply - powerful direct digital synthesis (DDS) type sine waveform generation, sine wave output pure, low harmonic distortion.
- Excellent stability - output load voltage stability ≤±1%, output frequency ≤0.01% (the output frequency is generated by quartz oscillation, so it has a very stable and accurate frequency).
- The reaction speed is fast - 100% load/deload, the output load can be stabilized in 2ms in the range of ±1%.
- Many protection functions - with overvoltage, overcurrent, over-high temperature, IGBT drive proprietary technology, output short-circuit protection to ensure that not damaged by short-circuit load.
- High overload capacity - 100% full load long-term use, instant current can withstand 3 times the rated current, and does not cause voltage drop, a variety of loads can be used.
- The human-machine interface is good - voltage, frequency, current, power/PF measurement digital display, accuracy up to 0.5 levels, source table integrated, simple operation.
Model | ACME 60-33060 | ACME 60-33100 | ACME 60-33150 | ACME 60-33200 | ACME 60-33300 | ACME 60-33450 | |||||
Capacity | 6KVA | 10KVA | 15KVA | 20KVA | 30KVA | 45KVA | |||||
Circuit model | IGBT/SPWM | ||||||||||
Input | Phase | Three phase | |||||||||
Voltage | 380v+-10% or customized | ||||||||||
Frequency | 50Hz/60Hz +-10% | ||||||||||
Output | Phase | Three phase | |||||||||
Wave | Pure sine wave | ||||||||||
Voltage | Phase vol. | L:0-150v H:0-300v | |||||||||
Wire vol. | L:0-260v H:0-520v | ||||||||||
Current | Low | 16.8A | 27.6A | 41.6A | 56A | 84A | 126A | ||||
High | 8.4A | 13.8A | 20.8A | 28A | 43A | 63A | |||||
Voltage stability | No more than 1% | ||||||||||
Load stability | No more than 1% | ||||||||||
Frequency | 50hz, 60hz, 45-65hz adjustable or customized | ||||||||||
Frequency stability | No more than 0.01% | ||||||||||
THD | No more than 2% | ||||||||||
Efficiency | No less than 94% at 100% load | ||||||||||
Reaction time | No more than 2ms | ||||||||||
Display | Frequency, voltage, current, power or PF 4 number display | ||||||||||
Protection function | over voltage, over current, over temperature, over load, short circuit, and automatic alarm | ||||||||||
Insulation resistance | >500Vdc 10MΩ | ||||||||||
Pressure endurance | 1800Vac/5mA/1minute | ||||||||||
Cooling model | Compulsive fan cooling | ||||||||||
Working temperature | -10ºC-45ºC | ||||||||||
Relative humidity | 0-90%(No condensing) | ||||||||||
Altitude | <1500meters |
Model | ACME 60-33600 | ACME 60-33750 | ACME 60-331000 | ACME 60-331500 | ACME 60-332000 | ACME 60-332500 | |||||
Capacity | 60KVA | 75KVA | 100KVA | 150KVA | 200KVA | 250KVA | |||||
Circuit mode | IGBT/SPWM | ||||||||||
Input | Phase | Three phase | |||||||||
Voltage | 380v+-10% or customized | ||||||||||
Frequency | 50Hz/60Hz +-10% | ||||||||||
Output | Phase | Three phase | |||||||||
Wave | Pure sine wave | ||||||||||
Voltage | Phase vol. | L:0-150v H:0-300v | |||||||||
Wire vol. | L:0-260v H:0-520v | ||||||||||
Current | Low | 168A | 208A | 276A | 400A | 556A | 694A | ||||
High | 84A | 104A | 138A | 200A | 278A | 347A | |||||
Voltage stability | No more than 1% | ||||||||||
Load stability | No more than 1% | ||||||||||
Frequency | 50hz, 60hz, 45-65hz adjustable or customized | ||||||||||
Frequency stability | No more than 0.01% | ||||||||||
THD | No more than 3% | ||||||||||
Efficiency | No less than 94% at 100% load | ||||||||||
Reaction time | No more than 2ms | ||||||||||
Display | Frequency, voltage, current, power or PF 4 number display | ||||||||||
Protection function | over voltage, over current, over temperature, over load, short circuit, and automatic alarm | ||||||||||
Insulation resistance | >500Vdc 10MΩ | ||||||||||
Pressure endurance | 1800Vac/5mA/1minute | ||||||||||
Cooling model | Compulsive fan cooling | ||||||||||
Working temperature | -10ºC-45ºC | ||||||||||
Relative humidity | 0-90%(No condensing) | ||||||||||
Altitude | <1500meters |
Model | ACME60-333000 | ACME60-334500 | ACME60-335000 | ACME60-336000 | ACME60-338000 | ||||||
Capacity | 300KVA | 450KVA | 500KVA | 600KVA | 800KVA | ||||||
Circuit mode | IGBT/SPWM | ||||||||||
Input | Phase | Three phase | |||||||||
Voltage | 380v+-10% or customized | ||||||||||
Frequency | 50Hz/60Hz +-10% | ||||||||||
Output | Phase | Three phase | |||||||||
Wave | Pure sine wave | ||||||||||
Voltage | Phase vol. | 0-300v adjustable | |||||||||
Wire vol. | 0-520v adjustable | ||||||||||
Current | 417A | 600A | 680A | 800A | 1050A | ||||||
Voltage stability | No more than 1% | ||||||||||
Load stability | No more than 1% | ||||||||||
Frequency | 50hz, 60hz, 45-65hz adjustable or customized | ||||||||||
Frequency stability | No more than 0.01% | ||||||||||
THD | No more than 3% | ||||||||||
Efficiency | No less than 94% at 100% load | ||||||||||
Reaction time | No more than 2ms | ||||||||||
Display | Frequency, voltage, current, power or PF 4 number display | ||||||||||
Protection function | over voltage, over current, over temperature, over load, short circuit, and automatic alarm | ||||||||||
Insulation resistance | >500Vdc 10MΩ | ||||||||||
Pressure endurance | 1800Vac/5mA/1minute | ||||||||||
Cooling model | Compulsive fan cooling | ||||||||||
Working temperature | -10ºC-45ºC | ||||||||||
Relative humidity | 0-90%(No condensing) | ||||||||||
Altitude | <1500meters |