Basic Info.
Model NO.
APV400
Stroke
Linear 10 to 130 mm; Rotory 30° to 100°
Flow Characteristic
Linear/Equal Percentage/Inverse Equal Percentage/
Position Feedback
4 to 20 Ma (Option)
Ambient Temperature
-30 to 80 ºC (-40ºC Option)
Connection
Thread
Air Supply Pressure
1.5 to 8.0 Bar
Air Supply Interface
1/4 NPT or RC1/4
Explosive-Proof
Ex Ia II T6 Ga
Transport Package
Carton Box
Trademark
HollySys
Origin
China
HS Code
7318190000
Production Capacity
10, 000 PCS/Year
Product Description
The APV400 intelligent valve positioner is based on the piezoelectric valve principle with HART communication. It converts the two wire 4~20mA control signal into pneumatic output to the actuator, which can be used for the control of pneumatic linear stroke or rotory stroke actuators, and drives the actuator to bring the valve to the position corresponding to the set value. This type of positioner has a compact design and a modular structural design, which is cost-effective. The self-tuning of the control parameters and the excellent adaptability of the positioner result in significant time savings and provide optimal control behavior.
Features
Technical Specification
Product Image
Packaging & Delivery
Related Products
A100 Globe Control Valve
A400 Ball Valve
A700Butterfly Valve Company Profile
Features
· Pneumatic system: adopt intelligent positioning module imported from Germany to control the pneumatic actuator. The module utilizes piezoelectric technology to achieve the highest energy efficiency and lowest air consumption. Pneumatic systems are available in single and double acting versions with fail safe/fail last.
· Fast Response and Precise Control: Adaptive predictive control algorithm for fast response and more precise control.
· Self-tuning function: automatically find the lower limit and upper limit of the valve, optimize the valve control parameters, and improve the precision of valve control.
· Display and operation: dot-matrix liquid crystal display, display content is more abundant. With 4 buttons, you can manually control the valve opening or make configuration settings locally.
· Configuration function: It can set parameters such as split range, characteristic curve, travel range, travel direction, tight closure, dead zone, control parameters, digital input, alarm output, fault output, and so on.
· Diagnostic Functions: Leakage detection, partial stroke test, upper limit and lower limit monitoring, pressure detection diagnosis, temperature diagnosis, stroke accumulation, number of direction changes, and number of piezoelectric runs.
· Communication protocol: HART5 and HART7 bus protocols.
· Digital input: one electrically isolated digital input, two dry contact inputs.
· Digital Outputs: Digital outputs with galvanic isolation are used to output alarm/trouble messages.
· Position feedback: The position feedback module with electrical isolation can output 4~20mA valve position feedback signal.
· Pressure diagnostic function: Measurement and diagnosis of air source pressure, drive pressure 1 and drive pressure 2. Technical Specification
Input signal | Actuator type | Single-acting, double-acting, linear stroke, rotory stroke pneumatic actuators |
Travel range | Linear stroke 10 to 130 mm; Rotory stroke 30º to 100° | |
Input control signal | Two-wired 4 to 20 mA DC | |
Load impedance | 455 Ω (without HART), 495 Ω (with HART) | |
Characterization | Linear/equal percentage/inverse equal percentage/customized | |
Communication method | HART communication protocol (optional) | |
Pneumatic parameters | Air supply | Air supply pressure 1.5 to 8.0 bar |
Compressed air quality according to ISO 8573-1; Requires filter unit class 4, oil content class 4, dew point class 4 (at least 10K below ambient temperature); The gas source should be free of visibly corrosive gases, vapors and oils. | ||
Output signal pressure | Minimum 0 bar, maximum air pressure | |
Rated flow rate | Inlet: ≥ 130 l/min (@25°C) 6→5 bar | |
Exhaust: ≥ 240 l/min (@25°C) 6→5 bar | ||
Chamber leakage | ≤ 0.05 l/min (@ 25°C) 6→0 bar | |
Steady-state gas consumption | ≤ 0.4 l/min (@ 25°C) | |
Accurate | Dead band | Automatic, 0.1 to 10.0% adjustable |
Fundamental error | 0.5% FS | |
Return differential (e.g. of farmland) | 0.5% FS | |
Repetitive | 0.2% FS | |
Response time | 20 ms | |
Human-computer interaction | Liquid crystal display | Dot-matrix liquid crystal display, can be displayed in English and Chinese and 180° flip display. |
Display content | Valve opening, input current, set value, operation mode and diagnostic status are displayed, and four display themes are available. | |
Pressure gauge display | Optional 2 to 3 pressure gauges can be used to display the inlet and outlet pressures. | |
Automatic initialization | Automatic initialization of valve lower and upper limits, minimum control pulses and optimization of control parameters, etc. | |
Diagnostic | Leak detection, partial stroke test, upper limit and lower limit monitoring, pressure monitoring, temperature monitoring, stroke accumulation monitoring, direction change count monitoring, and piezoelectric operation count monitoring are available. | |
Local operation | 4 keys for local manual control of valve opening or configuration settings. | |
Environmental parameters | Environmental temperature | T4: -30ºC to +80ºC; T5: -30ºC to +65ºC; T6: -30ºC to +50ºC (Low temperature -40°C optional) |
Environmental humidity | 5% to 95% | |
Vibration resistance | Withstand mechanical vibration with a vibration frequency of 10 Hz to 500 Hz, a displacement amplitude of 0.15 mm (10 Hz to 60 Hz) or an acceleration of 20 m/s2 (60 Hz to 500 Hz). | |
Protection class | IP65 | |
Explosion-proof symbol | Ex ia II C T4... .T6 Ga | |
Mechanical parameters | Pneumatic interface | Interface thread RC1/4 or 1/4 NPT |
Electrical interface | 2 pcs, interface thread M20 x 1.5, G1/2 or 1/2 NPT | |
Overall dimensions | 208 mm × 98 mm × 104 mm (excluding drive shaft attachment, blocking parts, manometer module) | |
Weights | About 2.0 kg | |
Digital input1 | Functionality | It has the functions of configuration locking, configuration and manual locking, partial travel test, controlling the valve to the start point of travel adjustment, controlling the valve to the end point of travel adjustment, and prohibiting valve movement. |
Electrical parameters | For floating contacts only, contact load 3 V DC 10 μA Status 0: Disconnected Status 1: Shorted | |
Digital input2 | Functionality | Functions for partial stroke testing, controlling the valve to the start of the stroke adjustment, controlling the valve to the end of the stroke adjustment, and prohibiting valve movement. |
Electrical parameters | Terminal X202 (23+, 24-) electrically isolated, input voltage range < 25 V DC state 0: input voltage ≤ 4.5 V or open state 1: input voltage ≥ 13 V | |
Terminal X203 (25+, 26-) for floating contacts only, contact load 3 V DC 10 μA Status 0: disconnected Status 1: shorted | ||
Alarm output | Functionality | Alarm threshold 1 and alarm threshold 2 can be set, and the low alarm parameters "MIN MAX", "MIN MIN" or "MAX MAX" can be selected; Alarm output methods such as "-MIN -MAX", "-MIN -MIN" or "-MAX -MAX" for high alarm parameters or alarm shutdown. |
Electrical parameters | 2 alarm outputs, electrically isolated. Input voltage range: ≤10.5 V DC Signal state: low, ≤ 1.2 mA Signal state: high, ≥ 2.1 mA | |
Auxiliary power supply: The switching threshold of the power supply is in accordance with EN 60947-5-6UAux = 8.2 VR i = 1 kΩ | ||
Fault output | Functionality | The low fault message output parameters "Fault", "FNA" and "FNAB" and the high fault message output parameters "-Fault", "-FNA" and "-FNAB" can be selected. Fault", "-FNA" and "-FNAB" are selectable for the low fault message output parameters "Fault", "FNA" and "FNAB" and "-FNAB" for the high fault message output parameters. |
Electrical parameters | 1 fault message output, electrically isolated. Input voltage range: ≤ 10.5 V DC Signal state: low, ≤ 1.2 mA Signal state: high, ≥ 2.1 mA | |
Auxiliary power supply: The switching threshold of the power supply is in accordance with EN 60947-5-6UAux = 8.2 VR i = 1 kΩ | ||
Position feedback module (Optional) | Supply voltage | Auxiliary powerUAux ~ 13.5 to 28 V DC with reverse protection |
Output signal | 4 to 20 mA | |
Load resistance Ω | ≤ (UAux[V]-13.5 V)/I[mA] × 1000 | |
≤ (UAux [V]-13.5 V)/I[mA] × 1000 | ||
Resolution (of a photo) | ≤ 0.1% | |
Transmission error | ≤ 0.3% | |
Temperature effect | ≤ 0.1%/10°C | |
Pressure measurement module(Optional) | For measurement and diagnosis of air source pressure and drive pressure. | |
Product Image