- Overview
- Product Parameters
- Packaging & Shipping
Basic Info.
Model NO.
789
Display Mode
Digital
Accuracy
0.05%
Theory
Electronic Meter
Power Source
AC and DC
Connection Type
Test Lines
Maximum Scale
19999
Range Conversion Type
AUTO RANGZ
Additional Measuring Item
Temperature
Display
LED
Model
789
Current Measurement Range
0 to 1 a AC or DC
Current Sourcing Range
0 to 20 Ma or 4 to 20 Ma
Electrical Specifications Frequency
to 19.999 kHz
Operating Temperature
-4 to 131°f (-20 to 55°c)
Dimensions
50 X 100 X 203 mm
Weight
1.6 Lbs (610 G)
Transport Package
UPS/DHL/FedEx
Specification
50 x 100 x 203 mm
Trademark
FLUKE
Origin
China
HS Code
9030899090
Production Capacity
50, 000 Pieces/Year
Packaging & Delivery
Package Size
32.00cm * 16.00cm * 12.00cm
Package Gross Weight
1.300kg
Product Description
Ideal for troubleshooting and calibrating current loop applications, this process meter is compatible with the Fluke Connect app, which enables compatibility technicians to wirelessly monitor, log, and share data from the field. Additionally, this tool can measure, source, and simulate mA.
Fluke 789 ProcessMeter with HART Communications/Diagnostics
- 24 V Loop power supply
- Very large dual display
- Enhanced backlight with 2 brightness settings
- 1200 Ohm drive capability on mA source
- HART mode setting with loop power and a built-in 250 ohm resistor
- 0% and 100 % buttons to toggle between 4 and 20 mA sourcing for a quick span check
- Externally accessible fuses for easy replacement
- Infrared-port to process data in FlukeView Forms (V2.1) software
- Precision 1000 V, 440 mA True-RMS digital Multimeter
- DMM designed to meet 1000 volt IEC 1010 CAT III standards
- Frequency measurement to 20 kHz
Current Measurement Range 0 to 1 A AC or DC Resolution 1 mA Accuracy 0.2% + 2 LSD (DC) Range 0 to 30 mA Resolution 0.001 mA Accuracy 0.05% + 2 lSD Current Sourcing Range 0 to 20 mA or 4 to 20 mA Resolution 0.05% of span Drive Capability 24 V Compliance or 1200 Ω at 20 mA Voltage Measurement Range 0 to 1000 V AC (True RMS) or DC Resolution 0.1 mV to 1.0 V Accuracy 0.1% Rdg + 1 LSD (VDC) Electrical Specifications Frequency To 19.999 kHz, 0.005% + 1 LSD Continuity Beeps for resistance <100 Ω Resistance Measurement To 40 MΩ, 0.2% + 1 LSD Diode Test 2.0 V shoes diode voltage drop Display Current and % of Span Yes Auto Step, Auto Ramp Yes Environmental Specifications Operating Temperature -4 to 131°F (-20 to 55°C) Storage Temperature -40 to 140°F (-40 to 60°C) Humidity (Without Condensation) 95% up to 86°F (30°C)
75% up to 104°F (40°C)
45% up to 122°F (50°C)
35% up to 131°F (55°C)Temperature Coefficient 0.05 x (specified accuracy) per °C (for temperatures <18°C or >28°C) Safety Specifications Electrical Safety Designed in accordance with IEC 1010-1, ANSI/ISA S82.01-1994 and CAN/CSA C22.2 No 1010.1-92 Overvoltage Category IEC 1010-1 CAT III 1000 V
IEC 1010-1 CAT IV 600 VMaximum Voltage 1000 V RMS Mechanical and General Specifications Batteries 4 x AA Alkaline batteries Battery Life 140 hours typical (measurement), 10 hours typical (sourcing 20 mA) Shock and Vibration Random, 2 g, 5 to 500 Hz
1 m drop testDimensions 1.25 x 3.41 x 7.35" (50 x 100 x 203 mm) Weight 1.6 lbs (610 g)