Basic Info.
Product Description
AMC series AC multi-function panel meter is a smart meter designed for power monitoring needs of power systems, industrial and mining enterprises, utilities, and intelligent buildings, etc. It integrates measurement of power parameters, such as single-phase or three-phase current, voltage, active power, reactive power, apparent power, frequency, power factor.
High-brightness LED/LCD display interface, parameter setting, and control through buttons, ideal for real-time power monitoring systems. Can directly replace conventional power transmitters and measuring instruments. As an intelligent, digital front-end acquisition component, the instrument has been widely used in various control systems, SCADA systems, and energy management systems.
AMC48 | AMC72 | AMC96 |
AMC48L | AMC72L | AMC96L |
Technical Parameter | Value | |
Input | Rated Value | AC voltage:Single phaseAC 100V,400V |
Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96) | ||
AC current:AC1A,5A; | ||
DC voltage:1000V,300V,75mV,10V; | ||
DC current: 0-20mA,4-20mA,5A; | ||
Overload | Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second | |
Current:1.2 times rated value(continuous); 10 times rated value /1 second | ||
Frequency | 45Hz~65Hz | |
Power Consumption | Power consumption of each voltage, the current input circuit is less than 0.5VA | |
Accuracy | Class 0.5 | |
Function | Display | LED or LCD |
Communication | RS485, Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) | |
Baud Rate 2400/4800/9600/19200 bps etc. | ||
Alarm | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. | |
Analog | DC4~20mA,( load <500Ω) | |
(note: Shielded wire is specially selected for the above signal input and output) | ||
Switching | Input:4 channel or 2 channel dry contact Input, built-in power supply | |
Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC | ||
Auxiliary Supply | AC/DC 85-265V | |
Power Consumption | <5VA | |
Insulation resistance | ≥ 100MΩ | |
Power frequency withstand voltage | Between power supply set of terminals and signal input, output set of terminals 2kV/1min (RMS) | |
Between the shell and all sets of terminals(except the set of terminals reference voltage less than 40V) AC 4kV | ||
Environment | Temperature | Operation: -10ºC~+55ºCStorage: -25°C ~+70°C |
Humidity | ≤95%RH, no condensation, without corrosive gas | |
Altitude | ≤ 2500m |